Input signal | RTDs and thermocouples |
Cold-end compensation temperature range | -20~70ºC |
Compensation accuracy | ±1ºC |
Output signal | 4~20mA, or 4~20mA plus HART protocol |
Load resistance | RL≤(Ue- 14)/0.021 |
Overflow alarm output current at the upper and lower limits. |
IH=21mA, IL=3.8mA |
Power supply | DC16~40V |
Temperature drift | 0.015%FS/ºC |
Response time | reaches 90% of the final scale within 1s |
Ambient temperature in use | -20~70ºC |
Dielectric strength | 1500Vrms(in 1 min) |
electrical insulation resistance | >=100MΩ (500VDC) |
Input type and transmission accuracy | |||||
Input | Code | Type | Measuring temperature Range | Min. measuring range | Conversion accuracy (whichever is greater) |
RTD | Pt100 | Pt100 | -200.0~850.0ºC | 20ºC | ±0.1%FS or ±0.2ºC |
Cu50 | Cu50 | -50.0~150.0ºC | 20ºC | ±0.1%FS or ±0.2ºC | |
TC(thermocouples) | TC-B | B | 400~1800ºC | 500ºC | ±0.1%FS or ±1.5ºC |
TC-E | E | -100~1000ºC | 50ºC | ±0.1%FS or ±0.5ºC | |
TC-J | J | -100~1200ºC | 50ºC | ±0.1%FS or ±0.5ºC | |
TC-K | K | -180~1372ºC | 50ºC | ±0.1%FS or ±0.5ºC | |
TC-N | N | -180~1300ºC | 50ºC | ±0.1%FS or ±0.5ºC | |
TC-R | R | -50~1768ºC | 500ºC | ±0.1%FS or ±1.5ºC | |
TC-S | S | -50~1768ºC | 500ºC | ±0.1%FS or ±1.5ºC | |
TC-t | T | -200~400ºC | 50ºC | ±0.1%FS or ±0.5ºC | |
Note: | |||||
1. The above accuracy data is tested under the condition of ambient temperature of 20ºC±2ºC. | |||||
2. The output accuracy "%" is relative to the set range. | |||||
3. Thermocouple measurement also need to add the cold end compensation error, internal cold end compensation error ≤ ± 1 ºC. |