Input signal | Resistance temperature detector (RTD), thermocouple (TC) |
Cold-junction compensation | -20 -60ºC |
Compensation precision | ±1ºC |
Output signal | 4-20mA with HART protocol |
Load resistance | RL≤(Ue- 12)/0.021 |
Output current of upper and lower limit overflow alarm |
IH=21mA, IL=3.8mA |
Supply voltage | DC12-40V |
Temperature drift | 0.0075%FS/ºC |
Response time | Reach 90% of the final value for700ms |
Used environmental temperature | -40 - 80ºC |
Storage temperature | -40 - 100ºC |
Insulation strength (between input and output) |
1500Vrms (1 min, without spark) |
Insulation resistance (between input and output) |
≥100MΩ(under the 500 VDC) |
Aseismicity | 4g/2 - 150Hz |
Installation angle | Unlimited |
Installation area | B-type top cassette installation |
Electromagnetic compatibility | Conform to GB/T18268 industrial equipment application requirements (IEC 61326- 1) |