Customization: | Available |
---|---|
Type: | 35mm DIN rail installation |
Measuring Medium: | Temperature |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
This product converts the thermal resistance or thermocouple signal on site into a DC signal that is linear with the temperature and outputs it to the control system after isolation and amplification. When used as a thermocouple temperature transmitter, it has the function of automatic cold end temperature compensation. The supporting host computer software can be used to modify the parameters. It can be used in conjunction with unit combination instruments and DCS, PLC and other systems to provide on-site instrument signal isolation, signal conversion, signal distribution, signal processing, etc., thereby improving the anti-interference ability of the industrial production process automatic control system and ensuring the stability and reliability of the system. This product variety is divided into one-input and one-output, two-input and two-output, and the input and output are magnetically isolated.
Input | RTD,TC |
Output | 4~20mA+HART |
Output load | RL≤(Ue-11)/0.021 |
Power supply | DC12~40V |
Power consumption | ≤1W with One way in, one way out |
Electrical isolation | U=2000VAC |
Circuit limit | ≤22mA |
Saturation current | Low end 3.8mA; High end 21mA |
Operating temperature | -20~60ºC25%~85%RH |
Relative humidity | 25%~85%RH |
Storage temperature | -20~60ºC |
Mounting method | 35mm DIN rail installation |
Mounting size | 13*108*121.2mm(width*height*depth) |
Response time | ≤1S |
Electromagnetic compatibility | Comply with GB/T18268 industrial equipment application requirements (IEC 61326-1) |
Applicable field equipment | Two or three-wire thermal resistor and thermocouple sensor |
Type | Measuring range | Min measuring range | Conversion accuracy (take the larger value) |
||
RTD | Pt100 | -200.0~850.0ºC | 20ºC | ±0.1% FS or ±0.2ºC | |
Cu50 |
-50.0~150.0ºC | 20ºC | ±0.1% FS or ±0.2ºC | ||
TC | B | 400.0~1800.0ºC | 500ºC | ±0.1% FS or ±1.5ºC | |
E | -100~1000ºC | 50ºC | ±0.1% FS or ±0.5ºC | ||
J | -100~1200ºC | 50ºC | ±0.1% FS or ±0.5ºC | ||
K | -180~1372ºC | 50ºC | ±0.1% FS or ±0.5ºC | ||
N | -180~1300ºC | 50ºC | ±0.1% FS or ±0.5ºC | ||
R | -50~1768ºC | 500ºC | ±0.1% FS or ±1.5ºC | ||
S | -50~1768ºC | 500ºC | ±0.1% FS or ±1.5ºC | ||
T | -200~400ºC | 50ºC | ±0.1% FS or ±0.5ºC |
Item NO. | Type | |||||
HTM215 | Temperature Transmitter(Rail type) | |||||
Code | Channel Numbers | |||||
11 | One input+one output | |||||
22 | Two inputs+two outputs | |||||
Code | Channel one Input type | |||||
0 | Thermocouple B | |||||
1 | Thermocouple S | |||||
2 | Thermocouple K | |||||
3 | Thermocouple E | |||||
4 | Thermocouple T | |||||
5 | Thermocouple H | |||||
6 | Thermocouple R | |||||
7 | Thermocouple N | |||||
11 | Thermal resistor CU50 | |||||
14 | Thermal resistor PT100 | |||||
Code | Channel two Input type | |||||
0 | Thermocouple B | |||||
1 | Thermocouple E | |||||
2 | Thermocouple J | |||||
3 | Thermocouple K | |||||
4 | Thermocouple N | |||||
5 | Thermocouple R | |||||
6 | Thermocouple S | |||||
7 | Thermocouple T | |||||
11 | Thermal resistor CU50 | |||||
14 | Thermal resistor PT100 | |||||
X | No channel two | |||||
Code | Channel one ouput | |||||
X | No ouput | |||||
0 | 4~20mA | |||||
Code | Channel two ouput | |||||
X | No ouput | |||||
0 | 4~20mA+Hart | |||||
Eg:HTM215-22-2-2-0-0.(Two-input and two-output, input signal: Thermocouple K , output signal: 4~20mA+Hart.) |