Input | ||||
Input signals | Current | Voltage | Resistance | Thermocouple |
Input Impedance | ≤250Ω | ≥500KΩ | ||
Maximum input current | ≤30mA | |||
Maximum input voltage | ≤6V | |||
Output | ||||
Output signals | Current | Voltage | Relay | 24V Distribution or feeder |
Output load capability | ≤500Ω | ≥250 KΩ (Note: Please replace the module with higher load capacity) |
AC220V/0.6 (small) DC24V/0.6A(small) AC220V/3A(big) DC24V/3A(big) refer to Note below. |
≤30mA |
Comprehensive parameter | ||||
Accuracy | 0.2%FS±1word | |||
Setting model |
|
|||
Display |
|
|||
Working environment | Ambient temperature: 0 ~ 50 ºC; Relative humidity: ≤ 85% RH. Far from strong corrosive gas |
|||
Power supply | AC 100 ~ 240V, (50/60HZ). DC 20 ~ 29V |
|||
Power | ≤5W | |||
Frame | Standard snap-on | |||
Communication | Standard MODBUS communication protocol, RS-485, communication distance up to 1 km, RS-232, communication distance up to 15 meters Note: When the instrument has communication function, it is best to use an active converter for the communication converter |
Specification size | Indexing number of Loop 1 Indexing number of Loop 2 |
|||
Code | width*height*depth | Code | Indexing type (measuring range) | |
A B C D E F H K L |
160*80*110mm(Horizontal) 80*160*110mm(Vertical) 96*96*110mm(Quadrate) 96*48*110mm(Horizontal) 48*96*110mm(Vertical) 72*72*110mm(Quadrate) 48*48*110mm(Quadrate) 160*80*110mm (Horizontal / with light bar) 80*160*110mm (Vertical / with light bar) |
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 55 56 |
Thermocouple B (400~1800ºC) Thermocouple S (0~1600ºC) Thermocouple K (0~1300ºC) Thermocouple E (0~1000ºC) Thermocouple T (-200.0~400.0ºC) Thermocouple J (0~1200ºC) Thermocouple R (0~1600ºC) Thermocouple N (0~1300ºC) Thermocouple F2 (700~2000ºC) Thermocouple Wre3-25 (0~2300ºC) Thermocouple Wre5-26 (0~2300ºC) RTD Cu50 (-50.0~150.0ºC) RTD Cu53 (-50.0~150.0ºC) RTD Cu100 (-50.0~150.0ºC) RTD Pt100 (-200.0~600.0ºC) RTD BA1 (-200.0~600.0ºC) RTD BA2 (-200.0~600.0ºC) Linear resistance 0~400Ω (-1999~9999) Remote Resistance 0~350Ω (-1999~9999) Remote Resistance 30~350Ω (-1999~9999) 0~20mV (-1999~9999) 0~40mV (-1999~9999) 0~100mV (-1999~9999) -20~20mV (-1999~9999) -100~100mV (-1999~9999) 0~20mA (-1999~9999) 0~10mA (-1999~9999) 4~20mA (-1999~9999) 0~5V (-1999~9999) 1~5V (-1999~9999) -5~5V (-1999~9999) 0~10V (-1999~9999)(Can not change to other input) 0~10mA square (-1999~9999) 4~20mA square (-1999~9999) 0~5V square (-1999~9999) 1~5V square (-1999~9999) Full switch (Notes1) Special specifications |
|
Transmission output of Loop 1 (OUT1) | ||||
Code | output type (Load resistance RL) | |||
X 0 1 2 3 4 5 8 |
No 4~20mA (RL≤600Ω) 1~5V (RL≥250KΩ) 0~10mA (RL≤1.2KΩ) 0~5V (RL≥250KΩ) 0~20mA (RL≤600Ω) 0~10V (RL≥4KΩ) Customized |
|||
Transmission output of Loop 2 (OUT2) | ||||
Code | output type (Load resistance RL) | |||
X 0 1 2 3 4 5 8 |
No 4~20mA (RL≤600Ω) 1~5V (RL≥250KΩ) 0~10mA (RL≤1.2KΩ) 0~5V (RL≥250KΩ) 0~20mA (RL≤600Ω) 0~10V (RL≥4KΩ) Customized |
|||
The number of alarm points (relay contact output) | ||||
Code | The number of alarm limits | |||
X 1 2 3 4 |
No 1 alarm 2 alarms 3 alarms 4 alarms |
|||
Communication output | ||||
Code | Communication Interface (communication protocol) | |||
X D1 D2 D3 |
No RS-485 communication Interface (Modbus) RS-232 communication Interface (Modbus) RS-232C printer interface |
|||
Feeder output | ||||
Code | Feeder output (output voltage) | |||
X 1P 2P |
No 1 feeder 2 feeders For example: "2P (12/24)" means Loop 1 is 12V, Loop 2 feeder output is 24V. |
|||
Power supply | ||||
Code | Voltage | |||
A D |
AC/DC 100~240V (50/60Hz) DC 20~29V |
|||
Notes | ||||
Code | Additional function (ignoring if no requests) | |||
Q | Addition, subtraction, multiplication and division operations |